                        PŘÍLOHA Č. 2  Základní (Standardní) Práce Pronajímatele
Visionarv: Proiect Building Standard

This document describes the standard of delivery of the project
Visionary - within the Shell & Core delivery provided by the
Landlord (Landlorďs Works). The building is designed in
accordance with Czech technical standards (ČSN) and in accordance
with specification described in this document.

1) Shell & Core building completed in accordance with LEED Platinum level and in accordance
     according with technical specification (Owner's Design Requirements + Execution Drawings)

2) Standard of interior climate:

Internal temperatures:___________      wínter (min)                summer (max)
Offices, retails:                      22°C +/- 1,5°C              24,5°C +/~ 1,5°C
Conference rooms, meeting rooms:       22°C +/- 1,5#C              24,5°C+A 1,5°C
Entrance Lobby / Reception (Floor 1):  21°C +/- 1,5°C
Corridors, staircases, lifts:          not controlled              24,5°C+/~ 1,5°C
Toilets:                               22°C +/- 1,5°C              not controlled
Showers:                               24°C +/- 1,5°C              not controlled
Parkíng, Storages:                     min.15 °CC                  not controlled
Storages:                              not controlled              not controlled
                                                                   not controlled

If outside temperature exceeds 32°C the difference of 6°C between external and internal
temperature will be kept. This applies to all premises.
Maximum aír velocity in the same zone as above: 0,20 m/s

Internal air humidity:            Summer max: not controlled
Winter min: 30% RH

Acoustics:

Noise attenuation between floors:                                  52 dB

Noise attenuation of interior partitions (tenants space perimeter): 45dB{without doors)

Noise attenuation of facade:           33 dB Southwest fagade, 38 dB northeast facade

Air exchange rate:

Offices      36m3/h per one working plače + 15% reserve for meeting rooms (41,4 m3/h)

             (air rate calculated for occupancy 6m2/person)

WC           ventilated air exhaust from WC - 85 m3/h

3) Surfaces

Floors                  self-leveling (poured) terazzo
Main Entrance Lobby:    self-levelíng (poured) terazzo
Floor Lift Lobby:       ceramic tiles
Toilets:                ratsed floor (chipboard panels, thickness 38 mm, 150 mm height) +
Offices:                carpets (DESSO Essence, 500 g/m2, 500 x 500 mm tiles)

                                                                                         1/6
Ceilings              wooden ceiling
Main Entrance Lobby:  gypsum board fiat ceiling
Floor Lift Lobby:     acoustic ceiling, gypsum board fiat ceiling, gypsum perforated ceiling
Offices:              acoustic ceiling, gypsum board fiat ceiling, gypsum perforated ceiling
Retails, Canteen:     gypsum board fiat ceiling
Toiiets:

Wails

Main Entrance Lobby: MDF cladding, glazed fagade, visible concrete on columns

Floor Lift Lobby:     glass cladding - lacobel white soft (TBD)

Concrete structures: columns - colorless paint, wails - gypsum board cladding or plaster +

                      white paint

Plasterboard structures: white paint

Toiiets:              ceramic tile, gypsum board cladding

Garages, storages: colorless paint on concrete and brick structures

4) HVAC

     General
     Building is delivered with centra! supply of fresh air (air-handling units), cool (chiller, coolers), heat
     (district heating connection). The machines are located in plant rooms and on the roof of the
     building. Main risers are placed in vertical installation shafts running through all floors. in office
     areas, main distribution branches on floors are located in installation channels in office corridors
     (except for heating - in the floor void). Connections to end devices (such as pipes and ducts for
     cooling beams, cabling for light fixtures and sensors, pipes for sprinklers, etc.) are in the
     suspended ceiling

     Ventilation
     Fresh air is provided through fourseparate main AHUs located on the roof. AHUs are equipped
     with heating and cooling coils connected to district heating and chillers and indirect heat
     exchanger systém. System is designed as a 100% outdoor air systém. Fresh air is delivered by
     AHUs into interior open spaces through active induction units (cooling beams). Induction units
     are equipped with dew point sensors connected to the Building Management System. Adjacent
     spaces such as corridors, restrooms, and secondary lobbies are ventilated by the main AHUs
     through supply grilles through the wails. All areas are directly exhausted by exhaust fans also
     located on the roof. Constant dimension of distribution air ducting designed for low-speed air
     flow and cooling beams.

     Cooling
     Screw compressor Compact chillers are located on the roof. Heat rejection is provided by dry
     coolers on the roof. Chilled water-liquid (35% ethylene glycol) is supplied through insulated piping
     to cooling coils in the AHUs and trough plate exchanger (glycol to water) to terminál passive active
     induction units (cooling beams) which are surface mounted to the ceiling in each floor. Constant
     dimension of distribution piping, cooling beams with electronically controíled vaives (merged in
     groups) - cooling systém: 17/20°C.

                                                                                              2/6
Heating

         Object is connected to the district heating (water/water).Exchange station is located on lst
         Basement Level (Floor -1) serve as a source of hot water which is suppiied through piping to
         heating coils in AHUs, heating coil in hot warm water tank and floor mounted radiators around
         perimeter of each floor. Radiators are controlled automaticaliy through BMS. Radiators are
         equipped with thermostatic valves with servo motors controlled also through BMS. Distribution
         piping is located within raised floor,

5) Electrical

         Su ppIv and distribution
         Building is equipped with 2 transfomners (2x 1.250 kVA) connected to public power supply systém.
         Main cabling is placed in vertícal instaliation shafts. Floor connection points are secured via busbar
         systém. Distribution boards forTenanťs Premises are located ínside common premises (shafts).
         Cabling for end devíces (light fixtures, sockets, sensors, low-voltage systems, etc.) is placed within
         raised floor or in suspended ceiling (mounted to concrete slabs or within instaliation channels),

         Emereencv back-up Power
         Back-up power generátor is installed on the roof. It is reserved only for the back-up of building
         operation systems (such as fire emergency). Back-up power generátor for Tenants is not designed
         and included in Standard Landlorďs Works. A space for Tenants' power generátor is allocated on
         the roof, There is spáre capacity for emergency distribution in the shafts.

         Lighting
         Offices areas will be equipped with LED light fixtures in suspended ceiling 300x1200. Lighting will
         be controlled by dedicated control systém (DALI), including day-light control, motion sensors,
         time scheduling and automatic switch-off. Emergency lighting is designed in accordance with
         Czech building standards.

         Illumination levels  500 lux
         Offices:             150 lux
         Corridors:           300 lux
         Lobby, Reception:    200 lux
         Sanitary, toilets:   150 lux
         Staircases:          100 lux
         Storages:            300/75 lux
         Garages:

         Power sockets
         Power sockets in office areas are placed in floor boxes (1 floor box per 2 work stations) see
         Appendix Electrical - floor boxes. There will be 2 power sockets (230V/16A) and space for 2 data
         sockets provided for each workplace within a floor box (density of workplaces is designed to 1
         workplace to 9m2) see Appendix Electrical - floor boxes. Designed electrical load 50W/m2 for
         sockets on office floor and 700W/m2 for IT technology including cooling demands (considering
         area for IT not bigger than 2,5 % of total office area).

                                          3/6
     Switches and controllers
     Light switches and thermo controllers will be instailed within pIasterboard partitions or on the
     surface of concrete walis / columns

     BMS
     Office areas are divided into 9 zones (Shell & Core / Standard Landíorďs Works). Each zone is
     controlled individually. Number of zones can be adjusted accordlng to fit-out requirements,
     Heating/ cooling in offices Is controlled via thermostats / controllers within BMS.

     External / internal blinds
     Building is not equipped with external shading systém, Interior shading is included in Standard
     Landíorďs Works. Ali blinds/louvers are manually controlled. Type of shading: horizontál lamellas,
    white color, width of lameila 5cm.

     Low-voltaee svstems
    The building is equipped with foilowing low-voltage systems:

                    Access Controi System - access cards and readers
                    CCTV - cameras on underground ffoors and ground fioor
                    Security systém ~ securing the shell of the building by magnetic sensors in the
                    perimeter doors.
                    Fire Alarm System - fire and smůke detectors, evacuation loudspeakers
                    Audio systems - toilets
                    TV/SAT “ The building is not deiivered with TV/SAT network, aeriais - subject to
                    Above Standard Landíorďs Works. Television signál (IPTV) available via data providers
                    or possibie cable TV operátor.

    Telecommunications
    Connections of data providers will finish in distribution boards in the dedicated plant room in
     underground floors. Connections between the distribution boards to Tenants' Premises are
    subject to fit-out works, via dedicated cable routes. Serve rooms including related mechanical and
     electrical equipment is subject to fit-out specification, not included in Landíorďs Works. Expected
     number of data providers: 4 (Cetín, Diai Telecom, T-Mobile, UPC)
    The building is connected to public telephone network. No telephone lineš or network is a part of
     delivery for Tenants - subject to fit-out works.
    The building is equipped with network securing GSM signál for mobile phones. The provider has
     not been determined yet.
     Intercom systém will be instailed in order to communicate between main reception and building
    entrance, garages.

6) Common toilets

     Fully fitted and finished toilets (two sanitary cores per fioor, except for ground fioor and
     underground floors). Toilets for disabled people are availabie on each upper floors. Water
     efficient and low flow fixtures will be ušed. Number and size of toilets, inciuding toilets for
     disabled people is designed in order to comply with Czech building standards and norms. Hot
     water is prepared centrally in building boiler room.

                                                                                                                                                                   4/6
7} Kitchenette
     Con nection pointsfor cold water, hotwaterand sewagewiil be provided withinTenanťs Premises
     (connection points are at shafts). Kitchenettes are not included in Standard Landlorďs Works.

8) Doors, Windows

     Main entrance to building is via mechanical revolving dooř (access to Entrance Lobby). Entrance
     doors to Tenanťs Premises will be equipped with access control systém (card reader) and
     electromechanical lock, including master key systém. There are located 4 possible entrances to
     tenanťs premises in each of two lift lobbies on the floor. Windows are not openable, apart from
     access doors to terraces,

9) Facades

     There is exterior modular fagade systém (glazed fa?ade with vertical lamellas and shadowboxes).
     In the ground floor is ušed raster fagade systém. Any exterior signage / logos are not included in
     Standard Landlorďs Works - subject to Tenanťs requirements and subject to separate Building
     Permit

10) Elevators

    There are 3 iifts ín each core (total 6) + 1 shuttle elevator in core A I. 4x 1000 kg (13 persons)
     operating between l st to 7thfloor, 2x evacuation lift 2275 kg (30 persons) operating between -3rd
     to 8thfloor and Ix 630 kg (8 persons) operating between -3rdto l st floor. Lifts are equipped with
     Destination Controi System (except shuttle liftwhich has conventionai control)

11) Fire Safety

     Fire and smoke detection systém, evacuation loudspeaker systém, sprinklers (wet systém),
     emergency lights, fire extinguishers. Fire resistance of structures (such as Windows, doors, walls,
     etc.) is designed to comply with Czech building Standards and reguiations, Fire ventilation is
     provided to protected routes. Emergency lighting in the underground floors and in the area of
     protected escape routes and in building Communications areas. Back-up power generátor
     designated for power supply to fire safety Systems in the event of fire.
     Wet sprinkler systém: spray systém 15mm, SSU/SSP heads K80, activating temperature 68°C.

12) Access /Security

    The building wiil provide access of 24 hours a day, 365 days a year. Tenant will háve a right to
     install his own security systém.

13) Floor numbering

     Numbering of all floors is according to Czech standards, e.g.:
    - Floor -3 (3rdundergroundfloor - 3,PP)
     - Floor -2 (2ndundergroundfloor - 2.PP)
     - Floor -1 ( lst undergroundfloor = l.P P }
     - Floor 1 (ground floor - 1,NP)
     - Floor 2 (2.NP), Floor 3 (3.NP), Floor 4 (4.NP), Floor 5 (5.NP), Floor 6 (6.NP), Floor 7 (7.NP)
     - Floor 8 (8thfloor = 8.NP)

                                                                                                                                                                   5/6
14) Appendíxes ~ plans (typical floor)    Floor pian / suspended ceilings
                                          Cooling beams
                    Architectural;        Radiators
                    Ventilation/Cooling:  Llght fixtures
                    Heatíng:              Floor boxes
                    Electrical:           Control zones
                                          Typical floor
               - BMS:                     Typical floor
                    Sprinklers:           Typical floor
                    Low voítage:
                    Water sewage:
Visionary: Proiect Common Premises Standard

This document describes the reference materials and types of
Products which are intended to be ušed in Common Areas delivered
by the Landlord within the Shell & Core delivery (Landlorďs Works).

1) Ground floor - Reception, Entrance Lobby
    Architectural design of the Entrance Lobby with the main building reception not yet compieted.
    Su rfa ces:

Two storey high lobby with sculptural spirál staircase, gaiíery with a gíass railing, vertical
greenery, design íight fixtures

        Floor:    Self-leveling {poured) terrazzo with light color, cleaning zone in the lobby and
                  revolving doors
       Walls:     MDF cladding, glazed fafade, exposed concrete columns, plaster on design
                  stairs to second floor.
       Ceilíng:   Wooden ceiling, solid gypsum board ceiling in corridors to lift lobbies.
Light fixtures:   Integrated/suspended light fixtures, architectural design
Other fixtures:   Air curtains, sprinklers, sensors, fire alarm, CCTV, emergency lighting and
                  signage (all ceiling mounted)
Doors:            Glazed entrance doors, glazed doors to retail units, wooden doors with MDF
                  cladding to common premises
Exit doors:       Aíuminum / Steel doors within fa^ade, dark grey frames
Revolving doors:  Manual, glazed, 4-section (to be confirmed)
Reception desk:   Architectural design of furniture, with additional equipment (coffee machine)
Access control:   Turnstiles (with card readers) + gate for disabled persons.

2) Typical fioors - Lift Lobby

Surfaces:

Floor: . Self-leveling (poured) terrazzo with light color

Walls:            Glass cladding Lacobel white soft color (elevator portál), Plaster/gypsum

                  board walls with white color

Ceiling: Solid gypsum board ceiling + white painting

Partitions:       Glazed partitions on second ground floor on the entrance to Tenanťs

                  Premises

Light fixtures: Down lights and spotlights píaced in ceiling, controlled via motion sensors

Other fixtures: Sensors, fire alarm, emergency lighting and signage (all ceiling mounted),

                  card readers (entrance to Tenanťs Premises)

Doors:            Glazed entrance doors to Tenanťs Premises, wooden doors to common

                  premises, white color
3) Typical floors - Toilets

Finál architectural design of toilets is notyet completed.

Surfaces:

         Floor: Ceramic tiles

         Walls: Ceramic tiles, mirrors

         Ceiling: Solid gypsum board ceiling + white paínting

Partitions:  Toilet cubicles made of plasterboard partitions (floor to ceiling)

Ught fixtures: Integrated down líghts, ceiling mounted spotlights. Lights controlled via

             motion sensors

Other fixtures: Sensors, fire alarm, rádio speakers, emergency iighting and signage (all ceiling

             mounted)

Doors:       Wooden doors + metal frames, white color

Sanitary equip.: Sinks, urinals, toilets, fixtures and other equipment (not yet sampled)

4) Roof terraces (Floor 7, 8)

Surfaces:    Floor - wooden decking, sport surface on running track

             Green roof with several types of greenery (not yet sampled),

             low-maintenance extensíve greenery

Handraíls:   Steel railing (white color) with stainless Steel mesh

5) Balconies and terraces

Surfaces:    Floor - wooden decking

             Ceiling-wooden cladding

Handrail:    Steel railing (white color) with stainless Steel mesh

Others:      Stand-alone greenery (not yet sampled)

6) Interior staircases (escape routes)

Surfaces (not yet sampled):

         Floor: exposed concrete + anti-dust paint

         Walls: exposed concrete + anti-dust paint, gypsum board with white color

         Ceiling: exposed concrete + anti-dust paint, Solid gypsum ceiling in r* underground

Light fixtures: ceiling or wall mounted light fixtures, controlled via motion sensors

Other fixtures: cabling, fire alarm, fire ventilation, emergency Iighting and signage

Doors:       Steel doors, Steel frame, grey color

Handrail:    Steel handrail with vertical bars

Elevators

Koně, MonoSpace 700, destination control systém with, availabíe combination with Access

Control System (possible restricted access to Tenanťs floors via access cards).

Interior fínishes: Glass cladding - lacquered, dimmed glass, stainless Steel ceiling with indirect

             lights, integrated spotlights, mirror, hand-rails

Capacity:    lx 30 persons + 2x 13 persons + lx 8 persons - shuttle (building AI), lx 30

             persons + 2x 13 persons (building A2)

                                                                                          2/4
8) Underground floors - Lift Lobby

Surfaces:

        Floor: Epoxy screed

        Walls: Gypsum board + white painting

        Ceiling: Solid gypsum board ceiling + white painting

Light fixtures: Ceiling mounted light fixtures, controlled via motion sensors

Other fixtures:  sprinklers, sensors, fire alarm, CCTV, emergency iighting and signage (aII

                 ceiling mounted)

Doors:           Glazed doors within the partition, grey color

9) Underground floors - Garages

Surfaces:

        Floor:   Epoxy coating, traffic signage and parking numbering

        Walls:   Exposed concrete + anti-dust paint, exposed masonry + anti-dust paint

        Ceiling: Exposed concrete

Light fixtures:  Suspended mounted light fixtures, controlled via motion sensors

Other fixtures:  Sprinklers, cabling, ducting, sensors, Fire Alarm, CCTV, traffic signage,

                 emergency Iighting and signage (all ceiling mounted)

Doors:           Metal doors, Steel frame, grey color

Entrance gate:   Entrance and exit gate controlled via Access Control Systems (access card /

                 readers)

10) Underground floors - Storages

Surfaces:

        Floor:   Epoxy coating

        Walls:   Exposed concrete + anti-dust pain, exposed masonry + anti-dust paint

        Ceiling: exposed concrete

Light fixtures:  Ceiling mounted light fixtures

Other fixtures:  sprinklers, cabling, ducting, sensors, fire alarm, emergency Iighting and

                 signage (all ceiling mounted)

Doors:           metal doors, Steel frame, grey color

11) Underground floors - Showers, Cloak Rooms

Architectural design of Shower and Cloak Rooms (bicycle facilities) is not yet compieted.

Surfaces:

        Floor:   ceramic tiles + epoxy screed

        Walls:   ceramictiies + painted walls, mirrors

        Ceiling: plain plasterboard + painting

Light fixtures:  Lights integrated in ceiling, controlled via motion sensors

Other fixtures:  sprinklers, sensors, fire alarm, emergency Iighting and signage (all ceiling

                 mounted)

Doors:           wooden doors + metal frames, white color

Sanitary equip.: sinks, toilets, showers and fixtures not yet specified

Bicycle racks:   Capacity - approx.42 bikes

Fumiture:        Lockers

                                                                                           3/4
12) Garden/Exterior atrium

Architectural design of gardep and exterior atrium is not yet completed.

Surfaces:                grass, stone mosaic tiles/ wooden decking, graveí paths, greenery, trees,

                         flowers, benches, lightings

Others:                  architectural islands with greenery, trees, flowers, outdoor lights, outside

                         seating, leisure area.

13) Fa$ade               Glazed fagade with white frames and whíte aluminum cladding. Vertica!
     Modularfagade:      glass elements on exterior side (Profilit)
                         On the ground floor structural fapade systém
     Structural fa$ade:  Interior blinds included (finál design is not yet completed)
     Interior biínds:    No exterior blinds
     Exterior blinds:

                                                                          4/4
Visionarv: Proiect Tenanťs Premises
Standard

This document describes the reference materials and
types of products which are intended to be ušed in
Tenanťs Premises delivered by the Landlord
(Landlorďs Works),

Floor:
     Raised floor - chipboard panels, thickness 38 mm, 150 mm height (reference: MERO type 5 GA 38).
     Maximum point load is 2 kN, Maximum area! load 3,5 kN/m2 (limit of concrete slab)
     Carpets - carpet tiles (DESSO Essence, 500 g/m2,500 x 500 mm)

Walls:
     Concrete structures - plaster + white paínt or gypsum plasterboard + white paint
     Plasterboard structures - white paint
     Fire-rated partition (division of a floor to fire compartments) - plasterboard partition
     Partition with security function - class RC3

Ceiling:
     Combination of solid gypsum, perforated acoustic and minerál tile suspended ceilings. All ceilings
     háve clear height 2800 mm.
    Suspended solid gypsum plasterboard ceilings in lift lobbies and corrídors -1 2 ,5 mm board thickness,
     white color.
     Perforated acoustic ceilings in certain corners of the building, where minerál tiles cannot be ušed.
     Minerál tile suspended ceilings in the open space - grid 1200x600 mm, 17 mm tile thickness, semi-
     concealed edge, white color, Alfa w = 0,9.

Light fixtures:
     Offices-rectangular LED light fixtures in suspended ceiling, daylíghtsensors, DALI systém with manual
     override, lighting control is part of BMS controller, 4000 K
     Corrídors - LED downlight fixtures controlled via motion sensors, 4000 K

Fire / Emergency fixtures:
Emergency lights, escape routes signage, smoke detectors, sound sirens, sprinklers, fire extinguishers.

Control fixtures:
     Lights in offices controlled by switches (reference: ABB) 1 switch per one control zone (see BMS layout
     in appendix), lights in corrídors controlled via motion sensors
     Thermostat (reference: Siemens, Honeyweil, Sauter, Johnson Controls) - (+-2 degree scheme)
     Internal louvres controlled manually

Power sockets:
               Power sockets in office areas are placed in floor. There will be 4 power sockets (230V/16A)
               and space for 4 data sockets provided within a floor box. Floor box reference: Legrand.
               Sockets for maintenance / cleaning are placed on walls / partitions - situated next to the
               entrances from lobby and staircases. Socket standard: ABB

                                                                                                                                                                          1/2
HVAC:
     Cooling beams are placed in the suspended ceiling - mounted to ceiling sfabs (reference: Halton,
     Flaktwoods, Swegon; white color)
     Radiators: low self-standing floor-mounted radiators (reference: ISAN, white color)
     Operation of HVAC can be adjusted on Client request. Addition Service charge will be proportionally
     calculated.
     Space reserve for tenant additional cooling (eg. server room) is situated of the roof - separated Circuit.

Doors
     Main entrance from lift lobby: glazed doors, height 2730 mm, width 900 mm, electromagnetic íock
     (reference Assa Abloy), access control systém (card reader), buílding master key
     Entrance to the balconies / terraces: glazed doors within fafade systém
     Doors in fire-rated partition (division of a floor to two fire compartments): wooden dooř, white color,
     CPL surface, height 2100 mm, width 900 mm, 30 min fire rating)
     Doors to terraces are equipped with electromagnetic contacts connected to secu rity systém.

Notě:
The amount of all terminál elements (cooling beams, lights, floor boxes, sockets etc.) are specified in the
appendix EXHIBIT 2a - Standard Landlorďs Works - Project Buílding Standard.